Item
SSTP/
STPE
Operation
of each
instruction
JP/
LOOP/LBL
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
FPWIN GR
Ladder symbol mode
A distance with the same number
cannot be defined twice.
An SSTP instruction cannot be
written in a subprogram.
Be sure to write the instruction for
setting the loop number before LBL-
LOOP instructions.
FPWIN GR
Boolean mode
Writing and deletion of a single
instruction is not possible for a
program with no step ladder area.
Write or delete both instructions
simultaneously in FPWIN GR ladder
symbol mode.
In the case of an SSTP instruction
only, writing and deletion of a single
instruction is possible for a program
with a step ladder area.
Write in the order: JP-LBL or
LOOP-LBL
Delete in the order: LBL-JP or LBL-
LOOP