6.6.3 Setting Communication Parameters: PC(PLC) Link
Settings for baud rate and communication format
The settings for baud rate and communication format of the COM port are entered using a programming
tool.
Setting with FPWIN GR
Select "Options" in the menu bar, and then select "PLC Configuration". Click the "COM Port" tab.
Dialog box of PLC system register setting
No. 410 Unit number
The unit number can be set within a range of 1 to 16.
No. 412 Communication Mode
Click on
, and select "PC Link".
Key Point:
When using a PC(PLC) link, the communication format and baud rate are fixed:
-
No.
Name
No. 413
Communication format
No. 415
Baud rate setting for COM1 port
Note) The settings of the baud rate switches on the side of the unit and the system register No. 415
should be the same.
6-34
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Set Value
Char. bit: ......
8 bits
Parity: .....
Odd
Stop bit: ............
1 bit
Terminator: ........
CR
Header: ............
STX not exist
115200 bps