14.1.2 Table of System Registers for FP-X0 L14 / L30 / L40 / L60
Add-
Item
ress
5
Starting number setting for counter
Hold type area starting number
setting for timer and counter
6
►For L40/L60
Hold type area starting number
7
setting for internal relays
►For L40/L60
Hold type area starting number
8
setting for data registers
►For L40/L60
Hold or non-hold setting for step
14
ladder process
►For L40/L60
Previous value is held for a leading
4
edge detection instruction (DF
instruction) with MC
Hold type area starting word No. for
PC(PLC) link relay (For PC(PLC)
10
link 0)
►For L40/L60
Hold type area starting word No. for
PC(PLC) link relay (For PC(PLC)
11
link 1)
►For L40/L60
Hold type area starting word No. for
PC(PLC) link register (For PC(PLC)
12
link 0)
►For L40/L60
Hold type area starting word No. for
PC(PLC) link register (For PC(PLC)
13
link 1)
►For L40/L60
Disable or enable setting for
20
duplicated output
Operation setting when an I/O
23
verification error occurs
Operation setting when an
26
operation error occurs
Wait time setting for multi-frame
31
communication
Timeout setting for SEND/RECV,
32
RMRD/RMWT commands
Constant value settings for scan
34
time
Note1) Data is retained only when installing a backup battery.
Note2) Without the battery, use at the default settings. If changing the settings, the "Hold/Non-hold"
operation becomes unstable.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Name
Default
value
L14/L30:250
L14/L30 : 0 to 256
L40/l60:1008
L40/L60 : 0 to 1024
1008
0 to 1024
248
0 to 256
7890
0 to 8192
Hold/
Non-hold
Non-hold
Hold/
Hold
Non-hold
0 to 64
64
128
64 to 128
128
0 to 128
256
128 to 256
Disabled
Disabled/Enabled
Stop
Stop/Continuation of operation
Stop
Stop/Continuation of operation
2600.0 ms
4 to 32760 ms
10000.0 ms
10 to 81900 ms
0: Normal scan
Normal scan
0 to 600 ms: Scans once each
specified time interval
Description