Panasonic FP-X0 L14R User Manual page 112

Table of Contents

Advertisement

Supported commands
Executable
instructions for
master
F146 (RECV)
F146 (RECV)
F146 (RECV)
F146 (RECV)
F145 (SEND)
F145 (SEND)
Cannot be issued
F145 (SEND)
F145 (SEND)
Cannot be issued
Cannot be issued
Table for MODBUS reference No. and FP-X0 device No.
MODBUS reference No.
Coil
Input
Holding register
Input register
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Code
Name (MODBUS
(decimal)
original)
01
Read Coil Status
02
Read Input Status
03
Read Holding Registers
04
Read Input Registers
05
Force Single Coil
06
Preset Single Register
08
Diagnostics
15
Force Multiple Coils
16
Preset Multiple Registers
22
Mask Write 4X Register
23
Read/Write 4X Registers
000001-001760
002049-006144
100001-101760
400001-408191
300001-300128
302001-302256
Name for FP0R
Read Y and R Coils
Read X Input
Read DT
Read WL and LD
Write Single Y and R
Write DT 1 Word
Loopback Test
Write Multiple Ys
and Rs
Write DT Multiple
Words
Write DT Mask
Read/Write DT
Data on BUS
(hexadecimal)
0000-06DF
0800-17FF
0000-06DF
0000-1FFF
0000-007F
07D0-08CF
Remarks
(Reference No.)
0X
1X
4X
3X
0X
4X
0X
4X
4X
4X
PLC device No.
Y0-Y109F
R0-R255F
X0-X109F
DT0-DT8191
WL0-WL127
LD0-LD255

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fp-x0 l40mrFp-x0 l60rFp-x0 l30rFp-x0 l60mr

Table of Contents