COM port (For L40MR and L60MR types)
Item
Interface
Communication mode
Transmission distance
Baud rate
Communication method
Synchronous method
Transmission line
Computer link
Trans-
mission
General-purpose
code
serial communication
Communication
format
(to be set by
system register)
Note4)
No. of connected units
Communication functions
Note1) When connecting a commercially available device that has an RS485 interface, please confirm
operation using the actual device. In some cases, the number of units, transmission distance, and
baud rate vary depending on the connected device.
Note2) The values for the transmission distance, baud rate and number of units should be within the
values noted in the graph below.
Note3) The settings of the baud rate switches on the side of the unit and the system register No. 415
should be the same. Only 19200 bps can be specified when the C-NET adapter is connected with
the RS485 interface.
Note4) The start code and end code can be used only in the general-purpose serial communication
mode.
Note5) Unit numbers should be registered by the system register.
Factory default settings
Port type
Tool port
COM port
Note:
As it is the non-isolated type, the potential difference between the power supplies of RS485 devices
should be 4 V or less. If it exceeds 4 V, the unit may not communicate. The large potential difference
leads to the damage to devices.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
RS485
1:N communication
Max. 1200 m
19200, 115200 bps
Two-wire, half-duplex transmission
Start stop synchronous system
Multicore shielded line
ASCII
ASCII, Binary
Data length
7 bits/8 bits
Parity
None/Even/Odd
Stop bit
1 bit/2 bits
Start code
STX/No STX
End code
CR/CR+LF/None/ETX
Note2) Note5)
Max. 99 units (32 units max. when C-NET adapter is connected.)
Computer link (master/slave)
Modem initialization
General-purpose serial communication
Modbus RTU (master/slave)
PC(PLC) link
Baud rate
Data length
9600 bit/s
8 bits
115200 bit/s
8 bits
Specifications
Note1) 2)
Note2) Note3)
Parity
Odd
Odd
Stop bit
1 bit
1 bit