Advanced commissioning
6.16 PID technology controller
Setting the technology controller
Parameter
p2200
r2294
p2253
p2264
p2257, p2258
p2274
p2280
p2285
Advanced settings
Table 6- 37
Parameter
In the factory setting, the output of the technology controller is limited to ± maximum speed. You must
change this limit, depending on your particular application.
Example: The output of the technology controller supplies the speed setpoint for a pump. The pump
should only run in the positive direction.
p2297
p2298
p2291
p2292
Table 6- 38
Parameter
p2267
p2268
p2269
p2271
230
Remark
BI: Technology controller enable (factory setting: 0)
1 signal:
Technology controller is enabled.
CO: Technology controller output signal
To interconnect the main speed setpoint with the technology controller output, set
p1070 = 2294.
CI: Technology controller setpoint 1 (factory setting: 0)
Setpoint for the technology controller.
Example:
p2253 = 2224: The inverter interconnects the fixed setpoint p2201 with the setpoint
of the technology controller.
p2220 = 1: The fixed setpoint p2201 is selected.
CI: Technology controller actual value (factory setting: 0)
Technology controller actual value.
Technology controller ramp-up time and ramp-down time (factory setting: 1 s)
Technology controller differentiation time constant T
The differentiation improves the rise time for very slow controlled variables, e.g. a
temperature control.
Technology controller proportional gain K
Technology controller integration time (integral time) T
Limiting the output of the technology controller
Remark
CI: Technology controller maximum limiting signal source (factory setting: 1084)
CI: Technology controller minimum limiting signal source (factory setting: 2292)
CO: Technology maximum limiting (factory setting: 100 %)
CO: Technology minimum limiting (factory setting: 0 %)
Manipulating the actual value of the technology controller
Remark
Technology controller upper limit actual value (factory setting: 100 %)
Technology controller lower limit actual value (factory setting: -100 %)
Technology controller gain actual value (factory setting: 100 %)
Technology controller actual value inversion (sensor type)
0:
No inversion
d
(factory setting: 1.0)
P
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 09/2017, FW V4.7.9, A5E31298649B AH
(factory setting: 0.0 s)
(factory setting: 30 s)
d