Appendix
A.5 Electromagnetic Compatibility
Table A- 14
EMC Phenomenon
Conducted emissions
(disturbance voltage)
Radiated emissions
Harmonic Currents
Table A- 15
Typical Harmonic Current (% of rated input current) at U
Note
Units installed within the category C2 (domestic) environment require supply authority
acceptance for connection to the public low-voltage power supply network. Please contact
your local supply network provider.
Units installed within the category C3 (industrial) environment do not require connection
approval.
370
Conducted disturbance voltage and radiated emissions
Converter type
Remark
All converters with integrated class A filters.
Article number:
6SL3517-1BE**-*A**
Converter frame sizes A and B with integrated class A
filter.
Article number:
6SL3517-1BE11-*A*0
6SL3517-1BE12-*A*0
6SL3517-1BE13-*A*0
6SL3517-1BE14-*A*0
6SL3517-1BE16-*A*0
6SL3517-1BE17-*A*0
6SL3517-1BE21-*A*0
In a domestic environment this product may cause
radio interference in which case supplementary miti-
gation measures may be required.
Harmonic Currents
5th
7th
11th
24
11
K
13th
17th
9
7
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 09/2017, FW V4.7.9, A5E31298649B AH
Level acc. to
IEC 61800-3
Category C2
First Environment -
Professional Use
Category C2
First Environment -
Professional Use
1 %
19th
23rd
6
5
25th
4
4