Select the I/O configuration to preassign the inverter interfaces.
Set the applicable motor standard and the inverter supply voltage.
Select the application for the inverter:
● "[0] Load cycle with high overload for applications requiring a high dynamic performance,
e.g. conveyor systems.
● "[1] Load cycle with low overload ..." for applications that do not require a high dynamic
performance, e.g. pumps or fans.
● [6], [7]: Load cycles for applications with encoderless 1FK7 synchronous motors.
Select your motor.
Enter the motor data according to the rating plate of your motor.
If you have selected a motor based on its article number, the data has already been entered.
Set the most important parameters to suit your application.
Technological use:
● [0]: In all applications that do not fall under [1] ... [3]
● [1]: Applications involving pumps and fans
● [2]: Applications with short ramp-up and ramp-down times. However, this setting is not
suitable for hoisting gear and cranes/lifting gear.
● [3]: Setting only for steady-state operation with slow speed changes. We recommend
setting [1] if load surges in operation cannot be ruled out.
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 09/2017, FW V4.7.9, A5E31298649B AH
Optimizing the closed-loop speed controller (Page 240)
V/f control (Page 233)
Commissioning
5.4 Quick commissioning