Set dynamic braking
Parameter
p0219
p2106
An application example for configuring a drive with braking resistor is provided in the
Internet:
Engineering braking chopper (braking resistor) operation
(https://support.industry.siemens.com/cs/ww/en/view/22101908)
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 09/2017, FW V4.7.9, A5E31298649B AH
Description
Braking power of the braking resistor (factory setting: 0 kW)
For p0219 > 0, the inverter deactivates the VDC_max controller.
For vector control, p0219 defines the regenerative power limit p1531.
Using p0219, you define the maximum braking power that the braking resistor must
absorb.
Elektrically braking the motor (Page 254)
For an excessively low braking power, the inverter extends the motor ramp-down time.
The SIZER PC tool supports you when calculating the braking power.
AUTOHOTSPOT
BI: External fault 1
p2106 = 722.x
Signal for monitoring the braking resistor overtemperature with digital
input x of the inverter.
Adapt the default setting of the inputs and outputs (Page 143)
Advanced commissioning
6.18 Elektrically braking the motor