Dynamic Braking - Siemens Sinamics G110M Operating Instructions Manual

Sinamics series distributed converter for simogear geared motors
Hide thumbs Also See for Sinamics G110M:
Table of Contents

Advertisement

Parameter
p1234
r1239
Table 6- 42
Parameter
p2100
p2101 = 6
The fault is assigned an index of p2100. Assign the same index of p2100 or p2101 to the fault and
fault response.
The inverter's List Manual lists in the "Faults and alarms" list the possible fault responses for every
fault. Entry "DCBRK" means that you may set DC braking as response for this fault.
DC braking voltages
The line supply voltage available to the Inverter determines the amount of rectified brake
voltage available for DC braking function. Listed in the following table are examples of the
correlation between the input AC voltage to the available DC voltage for the DC braking
function.
Line voltage
380 V AC
Rectified brake
171 V DC
voltage
The following formula can be use a guide to the rectified brake voltage that is available from
the line voltage:
Line voltage x 0.45 = Brake coil voltage
For example: 400 V AC x 0.45 = 180 V DC.
6.18.2

Dynamic braking

Typical applications for dynamic braking require continuous braking and acceleration
operations or frequent changes of the motor direction of rotation:
● Horizontal conveyors
● Vertical and inclined conveyors
● Hoisting gear
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 09/2017, FW V4.7.9, A5E31298649B AH
Description
DC braking start speed (factory setting 210000 rpm)
DC braking status word
.08
DC braking active
.10
DC braking ready
.11
DC braking selected
.12
DC braking selection internally locked
.13
DC braking for OFF1/OFF3
Configuring DC braking as a response to faults
Description
Set fault number for fault response (factory setting 0)
Enter the fault number for which DC braking should be activated, e.g. p2100[3] = 7860
(external fault 1).
Fault response setting (factory setting 0)
Assigning the fault response: p2101[3] = 6.
400 V AC
180 V DC
6.18 Elektrically braking the motor
440 V AC
480 V AC
198 V DC
216 V DC
Advanced commissioning
500 V AC
225 V DC
257