Selecting the fixed speed setpoint, binary
You set 16 different fixed speed setpoints. You precisely select one of these 16 fixed speed
setpoints by combining four selection bits.
Figure 6-41
Additional information about binary selection can be found in function diagram 3010 in the
List Manual.
Parameters to set the fixed speed setpoints
Parameter
p1001
p1002
...
p1015
p1016
p1020
p1021
p1022
p1023
r1024
r1025.0
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 09/2017, FW V4.7.9, A5E31298649B AH
Simplified function diagram when selecting the fixed speed setpoints, binary
Description
Fixed speed setpoint 1 (factory setting: 0 rpm)
Fixed speed setpoint 2 (factory setting: 0 rpm)
...
Fixed speed setpoint 15 (factory setting: 0 rpm)
Fixed speed setpoint mode (factory setting: 1)
1:
Direct
2:
Binary
Fixed speed setpoint selection bit 0 (factory setting: 0)
Fixed speed setpoint selection bit 1 (factory setting: 0)
Fixed speed setpoint selection bit 2 (factory setting: 0)
Fixed speed setpoint selection bit 3 (factory setting: 0)
Fixed speed setpoint effective
Fixed speed setpoint status
1 signal
Fixed speed setpoint is selected
Advanced commissioning
6.14 Setpoints