Modifying an existing address of a single slave within the Inverter will not affect the address
of the other slave.
To change an existing address of a slave, the following procedure should be performed:
1.
2.
3.
4.
5.
6.
7.
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 09/2017, FW V4.7.9, A5E31298649B AH
Plug the AS-i Programmer into the addressing socket of the Inverter
Turn the dial on the Programmer to the ADDR position. The display
will indicate that this mode has been selected.
Press the
button; the screen will display uSE and the number
of the lower addressed slave.
The existing slave addresses are shown at the bottom of the dis-
play.
Press the
and
Press the
button; the display now shows SEt.
The selected number will begin to flash.
Press the
and
number.
Press the
button to confirm the new address.
ProG is displayed briefly followed by confirmation of the address
change.
4.4 Connecting the inverter to the fieldbus
buttons to select the slave address number to be changed.
buttons to select the new slave address
Installation