Advanced commissioning
6.24 Monitoring the driven load
Parameter
p2182
p2183
p2184
p2186
p2188
p2190
p2191
p2192
p2193 = 4 or 5
See also
Rotation monitoring (Page 271)
274
Description
7:
A07891: Load monitoring, pump/fan blocked
A07892: Load monitoring, pump/fan without load
A07893: Load monitoring, pump leakage
8:
F07894: Load monitoring, pump/fan blocked
F07895: Load monitoring, pump/fan without load
F07896: Load monitoring, pump leakage
Load monitoring speed threshold 1
When using the control mode "U/f control" (p1300 < 10):
p2182 > 10% of the rated speed
When using the control mode "encoderless vector con-
trol" (p1300 = 20):
p2182 > p1755 (switchover speed, motor model)
Load monitoring speed threshold 2
Load monitoring speed threshold 3
Load monitoring torque threshold 1, lower
Load monitoring torque threshold 2, lower
Load monitoring torque threshold 3, lower
Load monitoring torque threshold, no load
Load monitoring delay time
When using the control mode "encoderless vector control" (p1300 = 20):
For operation with an induction motor: Set p2192 < 1 s or p1750.6 = 1 (the
closed-loop control does not change to open-loop controlled mode for blocked
motor)
For operation with synchronous and reluctance motors, the inverter sometimes
cannot detect a blocked motor.
Load monitoring configuration (factory setting: 1)
4: Pump monitoring: Differentiation between leakage and dry running
5: Fan monitoring: p2191 has no effect
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 09/2017, FW V4.7.9, A5E31298649B AH
The inverter inter-
polates linearly
between character-
istic points.