Siemens Sinamics G110M Operating Instructions Manual page 265

Sinamics series distributed converter for simogear geared motors
Hide thumbs Also See for Sinamics G110M:
Table of Contents

Advertisement

Using a KTY sensor, the inverter monitors the motor temperature and the sensor itself for
wire-break or short-circuit:
● Temperature monitoring:
The inverter uses a KTY sensor to evaluate the motor temperature in the range from -48°
C ... +248° C.
Use the p0604 or p0605 parameter to set the temperature for the alarm and fault
threshold.
– Overtemperature alarm (A07910):
– Overtemperature fault (F07011):
● Sensor monitoring (A07015 or F07016):
– Wire-break:
– Short-circuit:
Temperature switch
The inverter interprets a resistance ≥ 100 Ω as being an opened temperature switch and
responds according to the setting for p0610.
PTC sensor
The inverter interprets a resistance > 1650 Ω as being an overtemperature and responds
according to the setting for p0610.
The inverter interprets a resistance < 20 Ω as being a short-circuit and responds with alarm
A07015. If the alarm is present for longer than 100 milliseconds, the inverter shuts down with
fault F07016.
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 09/2017, FW V4.7.9, A5E31298649B AH
- motor temperature > p0604 and p0610 = 0
The inverter responds with a fault in the following cases:
- motor temperature > p0605
- motor temperature > p0604 and p0610 ≠ 0
The inverter interprets a resistance > 2120 Ω as a wire-break and outputs the alarm
A07015. After 100 milliseconds, the inverter changes to the fault state with F07016.
The inverter interprets a resistance < 50 Ω as a short-circuit and outputs the alarm
A07015. After 100 milliseconds, the inverter changes to the fault state with F07016.
6.21 Motor temperature monitoring using a temperature sensor
Advanced commissioning
265