Advanced commissioning

6.8 Quick Stop function

3. Move the rotary table to one of the two limit positions or open one of the limit switches
manually.
4. Specify a speed setpoint. We recommend that you use a fixed setpoint for the limit
position control.
5. Start the rotary table briefly.
6. If the rotary table has not traversed in the direction of the opposite limit position, invert the
speed setpoint in the inverter.
7. Set the mechanical position of the limit switch and the OFF3 ramp-down time so that the
rotary table stops in good time at each limit position.
You have adapted the limit position control to the application.
6.8
Quick Stop function
Overview
The Quick Stop function enables a load on a conveyor system to be detected and if Quick
Stop is enabled, stop the load on the conveyor section.
The load on the conveyor section moves towards a dedicated sensor, as shown in the figure
below.
Figure 6-16
The front edge of the load is detected by the sensor, which initiates the Quick Stop function.
180
Fixed speed setpoint as setpoint source (Page 218).
Conveyor example 1
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 09/2017, FW V4.7.9, A5E31298649B AH