Advanced commissioning
6.18 Elektrically braking the motor
DC braking initiated by a control command
DC braking when the motor is switched off
Settings for DC braking
Parameter
p0347
p1230
p1231
p1232
p1233
256
Description
Motor de-excitation time (calculated after quick commissioning)
The inverter can trip due to an overcurrent during DC braking if the de-excitation time is
too short.
DC braking activation (factory setting: 0)
Signal source to activate DC braking
0 signal: Deactivated
1 signal: Active
Configuring DC braking (factory setting: 0)
0
No DC braking
4
General release for DC braking
5
DC braking for OFF1/OFF3
14
DC braking below the starting speed
DC braking braking current (factory setting 0 A)
DC braking duration (factory setting 1 s)
Requirement:
p1231 = 4 and p1230 = control command, e.g.
p1230 = 722.3 (control command via DI 3)
Function:
1. The higher-level control issues the
command for DC braking, e.g. using DI3:
p1230 = 722.3.
2. DC braking starts.
If the higher-level control withdraws the com-
mand during DC braking, the inverter inter-
rupts DC braking and the motor accelerates to
its setpoint.
Requirement:
p1231 = 5 or p1230 = 1 and p1231 = 14
Function:
1. The higher-level control switches off the
motor (OFF1 or OFF3).
2. The motor brakes along the down ramp to
the speed for the start of DC braking.
3. DC braking starts.
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 09/2017, FW V4.7.9, A5E31298649B AH