Instruction Execution For Power Interruptions - Omron CP1H-X40D Operation Manual

Cpu unit sysmac cp series
Hide thumbs Also See for CP1H-X40D:
Table of Contents

Advertisement

Power OFF Operation
Power OFF Timing Chart
AC: 85% of rated voltage
DC: 90% of rated voltage
Power OFF detected signal
Program execution status
CPU reset signal
Description of Operation
Note
2-6-2

Instruction Execution for Power Interruptions

92
2. A momentary power interruption that lasts more than 10 ms for AC power
or more than 2 ms for DC power may or may not be detected.
85% of the rated voltage or less for AC power
90% of the rated voltage or less or DC power
0
0 to 10 ms for AC
0 to 2 ms for DC
Momentary power
interruption not detected
and operation continues.
Power supply
voltage
Power supply
voltage
The following timing chart shows the CPU Unit power OFF operation in more
detail.
Cyclic tasks or interrupt tasks
Power OFF detection time:
The time from when the power supply voltages drops to 85% or less of the rated
voltage for AC power or 90% for DC power until the power OFF condition is detected.
Holding time for 5 V internal power supply after power OFF detection:
The maximum time that the 5 V internal power supply voltage will be maintained after
the power OFF condition is detected. The holding time is fixed at 1 ms.
Power OFF will be detected if the 100 to 240 V AC power supply falls below
85% of the rated voltage or the DC power supply falls below 90% of the rated
voltage for the power OFF detection time (10 ms minimum for AC power and
2 ms minimum for DC power). The CPU reset signal will turn ON while the
internal power supply is being held and the CPU Unit will be reset.
The CP1H CPU Unit cannot use the power OFF interrupt task and cannot set
the power OFF detection delay time.
If power is interrupted and the interruption is detected when the CPU Unit is
operating in RUN or MONITOR mode, the instruction currently being executed
will be completed and then the CPU Unit will be reset.
10 ms
Greater than 10 ms for AC
Greater than 2 ms for DC
Operation will continue or stop
depending on whether or not a
momentary power interruption is
detected.
Operation always stopped
at this point regardless.
Holding time for 5 V internal
power supply after power
OFF detection: 1 ms
Power OFF detected
Power OFF Detection
Delay Time
AC: 10 ms
DC: 2 ms
Section 2-6
Time
Stopped