Quick-Response Inputs - Omron CP1H-X40D Operation Manual

Cpu unit sysmac cp series
Hide thumbs Also See for CP1H-X40D:
Table of Contents

Advertisement

Quick-response Inputs

5-4

Quick-response Inputs

Overview
PLC Setup
Bit Allocation for
Quick-Response
Inputs
X/XA CPU Units
322
The quick-response inputs can read pulses with an ON time shorter than the
cycle time (as short as 30 µs). Use the quick-response inputs to read signals
shorter than the cycle time, such as inputs from photomicrosensors.
Up to 8 quick-response inputs can be used in the X/XA CPU Units and up to 6
quick-response inputs can be used in the Y CPU Units.
Use the CX-Programmer to set a built-in input as a quick-response input in the
PLC Setup. Click the Built-in Input Tab to display the Interrupt Input settings
(at the bottom of the tab). Set the input function from Normal to Quick for each
input that will be used as a quick-response input.
The following diagrams show the input bits and terminals that can be used for
quick-response inputs in each CPU Unit.
The 8 input bits CIO 0.00 to CIO 0.03 and CIO 1.00 to CIO 1.03 can be used
as quick-response inputs.
Section 5-4

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cp1h-xa40dCp1h-y20dt-dCp1h

Table of Contents