Din Track Installation - Omron CP1H-X40D Operation Manual

Cpu unit sysmac cp series
Hide thumbs Also See for CP1H-X40D:
Table of Contents

Advertisement

Mounting
Note
Note
3-3-4

DIN Track Installation

1,2,3...
116
• Slide the yellow sliders at the top and bottom of each Unit to lock the
Units together.
If the sliders are not secured properly, the Unit may not function properly.
3. Attach the End Cover to the Unit on the far right side of the Rack.
Attach the End Cover to the Unit on the far right side of the Rack. An I/O bus
error will occur and CP1H CPU Unit will not operate in either RUN or MONI-
TOR mode if the End Cover is not connected. If this occurs, the following infor-
mation will be set in memory.
Name
I/O Bus Error Flag
I/O Bus Error Details
• Always turn OFF the power supply before connecting Units to each
other.
1. Use a screwdriver to pull down the DIN Track mounting pins from the back
of the Units, and mount the Units to the DIN Track.
Move the sliders toward the
back until they lock into place.
Address
A401.14
A404
Section 3-3
Lock
Release
Slider
Status
ON
0E0E hex