Serial Plc Links - Omron CP1H-X40D Operation Manual

Cpu unit sysmac cp series
Hide thumbs Also See for CP1H-X40D:
Table of Contents

Advertisement

Serial Communications
Note
6-1-5

Serial PLC Links

Overview
Note
CPU Unit Serial Gateway Function Specifications
Item
Pre-conversion data
FINS (via FINS network, Host Link FINS, toolbus, NT Link,
or CPU bus)
Conversion functions
FINS commands addressed to serial port 1 or 2 on the CPU
Unit are converted to CompoWay/F commands (after
removing the header) if the FINS command code is 2803
hex and to Modbus-RTU commands (after removing the
header) if the FINS command code is 2804 hex.
Post-conversion data
CompoWay/F command or Modbus-RTU command
Serial communications
1:N half-duplex
method
Maximum number of
31
nodes
Enabling serial commu-
Serial Gateway Mode
nications mode
Response timeout
The time from when a message converted to a different pro-
tocol is set until a response is received is monitored by the
serial gateway function.
Default: 5 s, User setting: 0.1 to 25.5 s
Note A FINS response code of 0205 hex (response time-
Send delay function
None
If a CJ-series Serial Communications Unit is connected via a CJ Unit Adapter,
messages can also be converted to Modbus-ASCII or Host Link FINS. Refer
to the SYSMAC CS/CJ Series Serial Communications Boards/Units Opera-
tion Manual (W336) for details.
Serial PLC Links can be used to allow data to be exchanged among CP1H
and CJ1M CPU Units via the RS-422A/485 or RS-232C Option Boards
mounted to the CPU Units without requiring special programming. The com-
munications mode in the PLC Setup must be set to the Serial PLC Link Mode
to enable this functionality.
• Either serial port 1 or 2 can be used. (See note.)
• Words are allocated in memory in the Serial PLC Link Words (CIO 3100
to CIO 3199).
• A maximum of 10 words can be transferred by each CPU1H CPU Unit,
but the number of linked words can be set to fewer words. (The size must
be the same for all CP1H CPU Units.)
Serial PLC Links cannot be used on serial ports 1 and 2 at the same time. If
one port is set as a Serial PLC Link slave or master, it will not be possible to
set the other port for a Serial PLC Link. A PLC Setup error will occur if an
attempt is made to set both ports for Serial PLC Links.
Specification
out) is sent to the source of the FINS command if a
timeout occurs.
Section 6-1
349