Scheduled Interrupts - Omron CP1H-X40D Operation Manual

Cpu unit sysmac cp series
Hide thumbs Also See for CP1H-X40D:
Table of Contents

Advertisement

Interrupt Functions
Restrictions
5-1-4

Scheduled Interrupts

Procedure
PLC Setup
198
When CIO 0.01 goes from OFF to ON 200 times, processing of the cyclic task
that is currently being executed will be interrupted and processing of interrupt
task 141 will start. When the interrupt task processing is completed, process-
ing of the interrupted ladder program will restart.
W0.00
0.01
Counter SV (in A533)
= 200 (00C8 hex)
Counter PV (in A537)
0
Counting enabled.
Inputs cannot be used for input interrupts when they are being used as gen-
eral-purpose (normal) inputs or quick-response inputs.
This function executes an interrupt task at a fixed time interval measured by
the CPU Unit's built-in timer. Interrupt task 2 is allocated to scheduled inter-
rupt.
Set the PLC Setup.
Write the ladder program.
Click the Timings Tab and set the input function to Scheduled Interrupt Inter-
val (the scheduled interrupt timer's units). The timing units can be set to 10
ms, 1 ms, or 0.1 ms. The scheduled interrupt timer SV is calculated by multi-
plying this interval setting by the timer SV set with MSKS(690).
Interrupt task 141
executed.
• Use the CX-Programmer to set the scheduled
interrupt timer units in the PLC Setup.
• Write the program allocated to interrupt task
2 (scheduled interrupt task).
• Use MSKS(690) to specify the timer SV.
Section 5-1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cp1h-xa40dCp1h-y20dt-dCp1h

Table of Contents