Temperature Sensor Units
452
Programming with BCD(24) Instruction
Always ON
P_On
Execution
condition
1000.00
P_EQ
P_EQ
2.15
2.15
Programming with SCL2(−) Instruction
Always ON
P_On
Execution
1000.00
condition
P_EQ
P_EQ
P_CY
P_CY
Detects completion of input 0 initialization.
CMP(020)
2
#7FFE
1000.00
ON when input 0 has been initialized
Detects an open-circuit alarm or Unit
CMP(020)
error by checking whether the error code
2
7FFF has been output.
#7FFF
ON when an open-circuit alarm or Unit
100.00
error has been detected for input 0.
BCD(024)
Stores positive BCD data in D0.
2
D0
MOV(021)
Stores #0000 in D1.
#0000
D1
−(410)
#0000
When input 0 converted value is negative
2
(#0000 minus two's complement = actual
value)
D0
BCD(024)
D0
Stores negative BCD data in D0.
D0
MOV(021)
#0001
Stores #0001 in D1 to indicate a
D1
negative number.
Detects completion of input 0
CMP(020)
initialization.
2
#7FFE
1000.00
ON when initialization complete.
CMP(020)
Detects an open-circuit alarm or Unit
error by checking whether the error
2
code 7FFF has been output.
#7FFF
ON when an open-circuit alarm has
100.00
been detected.
SCL2(486)
2
D10
Parameter settings for data conversion:
D0
MOV(021)
When the converted value is non-
negative, stores #0000 in D1.
#0000
D1
MOV(021)
When the converted value is
negative, stores #0001 in D1.
#0001
D1
Section 7-5