Auxiliary Area Allocations by Address
Address
Name
Words
Bits
A403
A403.00
Memory Error
to
Location
A403.08
A403.09 Memory Cas-
sette startup
Transfer Error
Flag
A403.10 Flash Mem-
ory Error Flag
A404
All
I/O Bus Error
Details
A406
All
PLC Setup
Error Location
A407
A407.00
Too Many I/O
to
Points, Details
A407.12
688
Function
When a memory error occurs, the
Memory Error Flag (A40115) is
turned ON and one of the following
flags is turned ON to indicate the
memory area where the error
occurred
A403.00: User program
A403.04: PLC Setup
A403.07: Routing Table
A403.08: CPU Bus Unit Settings
When a memory error occurs, the
CPU Unit will continue operating and
the ERR/ALM indicator on the front
of the CPU Unit will flash.
(The corresponding flag will be
turned OFF when the error is
cleared.)
ON when automatic transfer at star-
tup has been selected and an error
occurs during automatic transfer. An
error will occur if there is a transfer
error, the specified file does not exist,
or the Memory Cassette is not
installed.
(This flag will be turned OFF when
the error is cleared by turning the
power OFF. The error cannot be
cleared without turning the power
OFF.)
ON when the flash memory is physi-
cally destroyed.
Contains information on I/O bus
errors.
The CPU Unit will stop operating and
the ERR/ALM indicator on the front
of the CPU Unit will light.
(A401.04 (I/O Bus Error Flag) will
turn ON.)
(This information will be cleared
when the error is cleared.)
When there is a setting error in the
PLC Setup, the location of that error
is written to A406 in 4-digit hexadeci-
mal.
The CPU Unit will continue operating
and the ERR/ALM indicator on the
front of the CPU Unit will flash.
(A406 will be cleared when the
cause of the error is eliminated.)
Always 0000 hex.
Settings
Status
Status
after
at star-
mode
change
ON: Error
Cleared
Cleared
OFF: No error
ON: Error
Cleared
Cleared
OFF: No error
ON: Error
Cleared
Cleared
OFF: No error
0A0A hex:
Cleared
Cleared
CP-series
Unit error
0000 hex: CJ-
series Unit
error, 1st Unit
0001 hex: CJ-
series Unit
error, 2nd
Unit
0F0F hex: CJ-
series Unit
error,
unknown Unit
0E0E hex:
CJ-series Unit
error, no End
cover
0000 to 01FF
Cleared
Cleared
hexadecimal
0000 hex
Cleared
Cleared
Appendix D
Write
Related
timing
flags, set-
tup
tings
Refreshed
A401.15
when error
occurs.
Refreshed
---
when
power is
turned ON.
Refreshed
---
when error
is
detected.
Refreshed
A401.14
when error
is
detected.
Refreshed
A402.10
when error
occurs.
---
A401.11,
A407.13
to
A407.15