Advertisement

Analog I/O Units
432
1 to 5 V
The 1 to 5 V range corresponds to the hexadecimal values 0000 to 2EE0 (0 to
12000). The entire data range is FDA8 to 3138 (−600 to 12600). Inputs
between 0.8 and 1 V are expressed as two's complements. If the input falls
below 0.8 V, open-circuit detection will activate and converted data will be
8000.
Converted Data
Hexadecimal (Decimal)
3138 (12600)
2EE0 (12000)
0000 (0)
FDA8 (−600)
0 to 20 mA
The 0 to 20 mA range corresponds to the hexadecimal values 0000 to 2EE0
(0 to 12000). The entire data range is FDA8 to 3138 (−600 to 12600). A nega-
tive current is expressed as a two's complement.
Converted Data
Hexadecimal (Decimal)
3138 (12600)
2EE0 (12000)
−1 mA
0000 (0)
4 to 20 mA
The 4 to 20 mA range corresponds to the hexadecimal values 0000 to 2EE0
(0 to 12000). The entire data range is FDA8 to 3138 (−600 to 12600). Inputs
between 3.2 and 4 mA are expressed as two's complements. If the input falls
below 3.2 mA, open-circuit detection will activate and converted data will be
8000.
Converted Data
Hexadecimal (Decimal)
3138 (12600)
2EE0 (12000)
0000 (0)
FDA8 (−600)
0.8 V
5 V 5.2 V
1 V
0 mA
20 mA 21 mA
FDA8 (−600)
3.2 mA
0 mA
20 mA 20.8 mA
4 mA
Section 7-4