Error Status - Omron CP1H-X40D Operation Manual

Cpu unit sysmac cp series
Hide thumbs Also See for CP1H-X40D:
Table of Contents

Advertisement

Trouble Shooting
9-11-2 Trouble-shooting with Indicators and Error Code Display
ERR
Error
Indicator
Lit
CPU Unit service
monitoring error
Two option boards
(unit version 1.0)
installed
Option board error An error occurred in
Option board
memory error
Flashing
CPU Unit fatal
error
IP address setting
error
IP address table
error
IP Router table
setting error
Address
Disagreement
Logic error in
setting table
System setup Sum
check error
FINS/TCP setting
error

9-11-3 Error Status

Error code
Probably Cause
Service from the CPU
0002
Unit was not completed
within the fixed interval.
The monitoring time is
normally 11s.
Two option boards
---
have been installed on
the CPU Unit.
0601
the Ethernet Option
Board.
An error occurred in
0602
the Unit's non-volatile
memory itself. This
error will occur while
writing or reading the
error log, system setup,
identity data, MAC ID.
A fatal error occurred in
0015
the CPU Unit.
The IP address is set
021A
incorrectly.
The IP address table is
021A
set incorrectly.
The IP Router table is
021A
set incorrectly.
The node number set
021A
for the option board
does not agree with the
host ID in the IP
address. This probably
occurs when the
address conversion
method is set for auto-
matic address genera-
tion.
There is a logic error in
021A
the setting table.
The Checksum of Sys-
03D0
tem setup is incorrect.
The settings of
03C0
FINS/TCP are
incorrect.
The status of errors that occur at the Ethernet Option Board is reflected in CIO
relation area, Refer to 9-9-1 CIO Area Allocation, Error Status for details.
(hex)
Check and correct the CPU Unit's operating
environment.
Check whether the related DIP SW is on.
Refer to 9-8-2 Installation and Removing.
Note Recovery is possible for this error.
When operation is restored, it will
return to normal.
Uninstall the Ethernet Option Board in one
serial port of the CPU Unit and restart the
CPU unit.
Restart the CPU Unit. Replace the Ethernet
Option Board if the error recurs.
Restart the CPU Unit. Replace the Ethernet
Option Board if the error recurs.
Eliminate the cause of the error in the CPU
Unit.
Correct the IP address. Do not set any of
the following IP addresses.
• Host IDs that are all 0 or all 1.
• Network IDs that are all 0 or all 1.
• Subnetwork IDs that are all 1.
• Addresses beginning with 127 (7F hex).
Correct the IP address table.
Correct the IP Router table.
Make sure that the node number and the last
byte of the IP address are the same and then
set other host IDs to 0.
Change the address conversion method.
Recreate the data specified by the 2nd byte
of the detailed error code.
Reset the value of system setup area.
Restart the CPU Unit.
Refer to operation manual and set the
FINS/TCP setting correctly.
Section 9-11
Correction
585

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cp1h-xa40dCp1h-y20dt-dCp1h

Table of Contents