1.17 U: Monitors
No.
Name
(Hex.)
U2-13
Operation Status @ Fault
(008C)
U2-14
Elapsed Time @ Fault
(008D)
U2-15
SFS Output @ Fault
(07E0)
U2-16
q-Axis Current@Fault
(07E1)
U2-17
d-Axis Current@Fault
(07E2)
U2-19
ControlDeviation@Flt
(07E4)
U2-20
Heatsink Temp @Fault
(008E)
U2-21
STPo Detect @ Fault
(1166)
Expert

U3: Fault History

No.
Name
(Hex.)
U3-01 to U3-04
1st to 4th MostRecent Fault
(0090 - 0093)
(0800 - 0803)
U3-05 to U3-10
5th to 10th MostRecent Fault
(0804 - 0809)
116
V/f
CL-V/f
OLV
CLV
AOLV
Shows the status of the MFDO terminals at the most recent fault where 1 = (ON) and 0 = (OFF).
For example, U2-13 shows "00000001" during run.
Use U1-12 [Drive Status] to monitor the actual MFDO terminal status.
bit 0 : During Run
bit 1 : During zero-speed
bit 2 : During reverse
bit 3 : During fault reset signal input
bit 4 : During speed agreement
bit 5 : Drive ready
bit 6 : During minor fault detection
bit 7 : During fault detection
V/f
CL-V/f
OLV
CLV
AOLV
Shows the cumulative operation time of the drive at the fault that occurred most recently.
Use U4-01 [Cumulative Ope Time] to monitor the actual cumulative operation time.
Unit: 1 h
V/f
CL-V/f
OLV
CLV
AOLV
Shows the output frequency after soft start at the fault that occurred most recently.
Use U1-16 [SFS Output Frequency] to monitor the actual output frequency after soft start.
Unit: 0.01 Hz
V/f
CL-V/f
OLV
CLV
AOLV
Shows the q-axis current of the motor at the fault that occurred most recently.
Use U6-01 [Iq Secondary Current] to monitor the actual q-Axis current of the motor.
Unit: 0.1 %
V/f
CL-V/f
OLV
CLV
AOLV
Shows the d-axis current of the motor at the fault that occurred most recently.
Use U6-02 [Id ExcitationCurrent] to monitor the actual d-Axis current of the motor.
Unit: 0.1 %
V/f
CL-V/f
OLV
CLV
AOLV
Shows the amount of control axis deviation (Δθ) at the fault that occurred most recently.
Use U6-10 [ContAxisDeviation Δθ] to monitor the actual amount of control axis deviation (Δθ).
Unit: 0.1 °
V/f
CL-V/f
OLV
CLV
AOLV
Shows the heatsink temperature at the fault that occurred most recently.
Use U4-08 [Heatsink Temperature] to monitor the actual temperature of the heatsink.
Unit: 1 °C
V/f
CL-V/f
OLV
CLV
AOLV
Monitors conditions to detect STPo [Motor Step-Out Detected] faults. The bit for each condition is
displayed as ON or OFF.
bit 0 : Excessive current
bit 1 : Induced voltage deviation
bit 2 : d-axis current deviation
bit 3 : Motor lock at startup
bit 4 : Acceleration stall continue
bit 5 : Acceleration stall repeat
bit 6 : Not used (normal value of 0).
bit 7 : Not used (normal value of 0).
V/f
CL-V/f
OLV
CLV
AOLV
Shows the fault history of the first to fourth most recent faults.
Note:
The drive saves the U3-01 to U3-04 [1st to 4th MostRecent Fault] fault histories to two types of
registers at the same time for the MEMOBUS/Modbus communications.
V/f
CL-V/f
OLV
CLV
AOLV
Shows the fault history of the fifth to tenth most recent faults.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
MFAO Signal Level
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
MFAO Signal Level
No signal output available
No signal output available