START-UP
4.3.3 Start-up
Operation via Keypad -
Control Mode:
Vector (P202=2)
ACTION
Power-up inverter
Press
. key. Press the
until P000 is reached. You can also
use the key
to reach the
Paramater P000.
Press the
key to enter into the
programming mode.
Use the keys
and
set the passowrd value.
Press the
key to save the
selected option and to exit the
programming mode.
Press the key
or
P202 is reached.
Press the
key to enter into the
programming mode.
Use the
and
select the control type
Press the
to save the selected
option and to start the tuning routine
after changing to Vector Control mode
Press the
key and use the keys
keys
and
correct rated motor efficiency (in this
case 71%)
56
The sequence below is based on the following inverter and motor example:
Inveter: CFW080040S2024ESZ
Motor: WEG-IP55
NOTE!
The notes in Table below can be found on page 60.
HMI DISPLAY
key
to
until
keys to
to set the
Power: 0.75HP/0.55kW;
Frame size: 71; RPM: 1720; Number of Poles: IV;
Power factor (cos ϕ): 0.70;
Efficiency (η): 71%;
Rated Current at 220V: 2.90A;
Frequency: 60Hz.
Inverter is ready to be operated
P000=access for changing parameters
Enter the programming mode
P000=5: permits parameter changing
Exit the programming mode
This parameter defines the control type
Enter the programming mode
P202=2: Vector
Motor efficiency:
Set motor efficiency:
DESCRIPTION
0=V/F Linear
1=V/F Quadratic
2=Vector
50 ... 99,9%
71%