WEG CFW08 Vector inverter User Manual page 152

Vector frecuency inverter
Table of Contents

Advertisement

CFW-08 OPTIONS AND ACCESSORIES
Parameter Number
P000
P001
P100
Number of the
Basic Variable
V00
V01
V05
Bit Number
Bit 0
Bit 1
Bit 7
Bit Number
Bit 100
Bit 101
Bit 107
Note: All registers (parameters and basic variables) are considered as
holding type registers, referenced from 40000 or 4x, whilst the bits are
referenced from 0000 or 0x.
The status bits have the same functions of the bits 8 to 15 of the logic
status (basic variable 2). These bits are available only for read, thus any
attempt to write command returns error status to the master.
Bit Number
Bit 0
Bit 1
Bit 2
Parameters
Endereço Modbus
Decimal
0
1
100
Basic Variables
Modbus Address
Decimal
5000
5001
5005
Status Bits
Modbus Address
Decimal
00
01
07
Commands Bits
Modbus Address
Decimal
100
101
107
Status Bits
Function
0 = Ramp enabling inactive
1 = Ramp enabling active
0 = General enabling inactive
1 = General enabling active
0 = Counter-clockwise direction of rotation
1 = Clockwise direction of rotation
Hexadecimal
0000h
0001h
0064h
Hexadecimal
1388h
1389h
138Dh
Hexadecimal
00h
01h
07h
Hexadecimal
64h
65h
6Bh
151

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cfw08 plus

Table of Contents