DETAILED PARAMETER DESCRIPTION
[Factory Setting]
Parameter
P303
Skip Frequency 1
0.01Hz (<100.0Hz);
P304
Skip Frequency 2
0.01Hz (<100.0Hz);
P306
Skip Band Range
(1)
P308
Inverter Address
(1)
This parameter can be changed only with the inverter disabled (motor stopped).
98
Range
Unit
Description / Notes
P133...P134
This feature (skip frequencies) prevents the motor from operating
[ 20.00Hz ]
permamently at speeds where the mechanical system enters into
resonance, causing high vibration or noise levels.
0.1Hz (99.99Hz)
The enabling of this function is performed by setting P306 0.00.
P133...P134
[ 30.00Hz ]
0.1Hz (99.99Hz)
0.00...25.00Hz
[ 0.00 ]
0.01Hz
The passage through the skip speed band (2xP306) is made
according to the selected acceleration/deceleration rates.
This function does not operate properly when two skip frequencies
are overlapped.
Sets the address of the inverter for the serial communication.
1...30
See item 8.18 and 8.19.
(WEG Protocol)
The serial interface is an optional inverter accessory.
1...247
See items 8.9, 8.10 and 8.13 for detailed information.
(Modbus-RTU)
[ 1 ]
1
Output
Frequency
2 x P306
P304
P303
Figure 6.23 - Skip Frequency" curves
2 x P306
Frequency
Reference
≠