WEG CFW08 Vector inverter User Manual page 104

Vector frecuency inverter
Table of Contents

Advertisement

[Factory Setting]
Parameter
P409
Motor Resistance
This
parameter is shown
of the display only
when in Vector
Control (P202=2)
Range
Unit
Description / Notes
0.00...9.99
Value estimated by the Self-Tuning routine.
[ According to
The table in item 9.3 shows the stator resistance for standard, IV
the inverter type ]
pole, 60Hz, 220/380V motors.
0.01
The value of the stator resistance can also be entered at P409 directly,
if this value is known.
DETAILED PARAMETER DESCRIPTION
NOTE!
P409 shall contain the equivalent value of the stator resistance
of one phase, by supposing that the the motor is star
connected (Y).
NOTE!
If the value of P409 is to high for the motor, a disabling of the
inverter can occur due to overcurrent (E00).
103

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cfw08 plus

Table of Contents