DETAILED PARAMETER DESCRIPTION
Parameter
P236
Analog Input AI1
Offset
P238
Analog Input AI2
Gain
This parameter
is only available in
the CFW-08 Plus
version
(1)
P239
Analog Input AI2
Signal
This parameter
is only available in
the CFW-08 Plus
version
P240
Analog Input AI2
Offset
This parameter
is only available in
the CFW-08 Plus
version
P248
Analog Inputs Filter
Time Constant
P251
Analog Output AO
Function
P252
Analog Output AO
Gain
These
parameters are
only available in
the CFW-08 Plus
version
(1)
This parameter can be changed only with the inverter disabled (motor stopped).
88
Range
[factory Setting]
Unit
Description / Notes
-120...120%
See P234.
[ 0.0 ]
0.1 (<100);
1 (>99.9)
0.00...9.99
See P234.
[ 1.00 ]
0.01
0...1
See P235.
[ 0 -
0...10V/0...20mA]
-120...120%
See P234.
[ 0.0 ]
0.1 (<100);
1 (>99.9)
0...200ms
[ 200ms ]
1ms
P251 defines the variable to be indicated at the analog ouput.
0...9
[ 0 - f
]
s
-
0.00...9.99
[ 1.00 ]
0.01
For factory Setting, AO=10V when the output frequency is equal to
maximum frequency (defined by P134), i.e., equal to 66Hz.
Indication scale at the analog outputs (full scale =10V):
It configures the time constant of the analog inputs filter between 0
(without filtering) and 200ms.
Thus the analog input will have a response time equal to three time
constants. For instance, if the time constant is 200ms, and a step
is applied to the analog input, the response will be stabilized after
600ms.
P251
0
Output frequency (Fs) - P005
1
Frequency reference or input frequency (Fe)
2
Output current - P003
3, 5 and 8
No function
4
Torque - P009
6
Process variable - P040
7
Active current
9
PID Setpoint
NOTE!
-Option 4 is only available in the vector control mode.
-Options 6 and 9 are only available from Software Version V3.50 on.
AO Function