WEG CFW08 Vector inverter User Manual page 59

Vector frecuency inverter
Table of Contents

Advertisement

START-UP
ACTION
Press the
key to go to the next
parameter
Press the
key and use the key s
and
to set the the correct
motor power.
Press the
key to save the
selected option and exit the
programming mode
Press the
key to got to the next
parameter
Press the
key and use the keys
and
to set the correct
motor power factor (in this case 0.70)
Press the
key to save the
selected option and exit the
programming mode
Press the
key to go to the next
parameter
Press the
key and use the keys
and
to authorize or not
the start of the parameter estimate
Press the
key to start the self-
tuning routine. While the self-tuning routine
is running, the display shows "Auto".
The running of the Self-Tuning Routine
can last until 2 minutes and after
ending display will show "rdy" (ready),
when the motor parameter were
acquired with success. Otherwise the
fault "E14" is shown. In this case refer
(1)
to Note
below.
Press the
key
Press the
key and hold it
depressed until the speed of 1980rpm
is reached
58
HMI DISPLAY
OR
DESCRIPTION
Rated motor power range:
0 ... 15 (each value represents a
power value)
Selected rated motor power:
4 = 0.75HP / 0.55kW
Exit the programming mode
Motor power factor range:
0.5 ... 0.99
Set motor power factor:
0.70
Exit the programming mode
Parameter estimation?
0 = No
1 = Yes
1 = Yes
Self-tuning is running
Inverter finished the self-tuning routine
and is ready for operation
or
Running of self-tuning routine has not
been realized with success
Motor accelerates up to 90rpm (for IV
pole motor - minimum speed) in CW
(3)
direction of rotation
Motor accelerates up to 1980rpm (for IV
pole motor - maximum speed)
(1)