INSTALLATION AND CONNECTION
CCW
CCW
CW
CW
-
RPM
+
38
Conector XC1
1
DI1
2
DI2
3
DI3
4
DI4
5
GND
6
AI1
7
+10V
8
AI2
9
AO
10
NF
11 Comum
12
NA
Figure 3.9 - XC1 control terminal description of the control board 1 (CFW-08 Plus)
Figure 3.10 - Dip switch position for 0 ...10V/4 ... 20mA selection
Description
Factory Default Function
Digital Input 1
General Enable (remote mode)
Digital Input 2
FWD / REV (remote mode)
Digital Input 3
Reset
Digital Input 4
Start/Stop (remote mode)
0V Reference
Analog input 1
Frequency/Speed reference (remote mode)
Potentiometer reference
Analog input 2
Not used
Analog output
Output Frequency (Fs)
Relay Output 2 - NC contact
Fs>Fx
Relay outputs common points
Relay Output 1 - NO contact
No Fault
Specifications
4 isolated digital inputs
Minimum High Level: 10VDC
Maximum Low Level: 3VDC
Input Current: -11mA @ 0V
Max. Input Current: -20 mA
Not connected to PE
0 to 10VDC or 0(4) to 20mA (fig. 3.10).
Impedance: 100kΩ (0...10V input), 500Ω
(0/4...20mA input).
Resolution: 7bits.
Max. input voltage: 30VDC
±
+10VDC,
5%, capacity: 2mA
0 to 10VDC or 0(4) to 20mA (fig. 3.10).
Impedance: 100kΩ (0...10V input), 500Ω
(0/4...20mA input).
Resolution: 7bits.
Max. input voltage: 30Vdc
0 to 10VDC, RL ≥ 10k Ω
Resolution: 8bits
12
10
Relé 1
11
Contact capacity:
0.5A / 250VAC
S1
1
2
OFF
ON
Relé 2