[Factory Setting]
Parameter
P208
Reference Scale
Factor
P215
(1)
Copy Function
This
parameter is only
available via
HMI-CFW08-RS
keypad
(1)
This parameter can be changed only with the inverter disabled (motor stopped).
Range
Unit
Description / Notes
It allows that the read-only parameter P002 indicates the motor
0.00...99.9
speed in value, for instance, rpm.
[ 1.00 ]
The indication of P002 is equal to the output frequency value (P005)
0.01 (<10.0)
multiplied by the value of P208, i.e., P002 = P208 x P005.
0.1 (>9.99)
If desired, the conversion from Hz to rpm is made as a function of
the pole number:
Always when programmed to vector mode (P202=2), the parameter
P208 is set according to the value of P402 (motor speed) to indicate
the speed in rpm, in P002.
0...2
The keypad Copy function is used to transfer the content of the
[ 0 - No function ]
parameters from one inverter to another.
-
P215
Procedure is as follows:
1. Connect the keypad (HMI-CFW08-RS) to the inverter from which
2. Set P215=1 (copy) to transfer the parameter values from the
3. Disconnect the keypad from the inverter (A).
4. Concect the same keypad to the inverter to which the
5. Set P215=2 (paste) to transfer the content of the of the keypad
DETAILED PARAMETER DESCRIPTION
Motor Pole Number
II poles
IV poles
VI poles
Action
0
Off
Copy
1
(inverter→ keypad)
Paste
2
(keypad → inverter)
the parameters willl be copied (Inverter A - source inverter).
inverter A to the keypad. Press
Copy Function, display will show
P215 resets automatically to 0 (Off) after transfer has been
completed.
parameters will be transferred (Inverter B - target inverter).
(EEPROM has the inverter A parameters) to inverter B.
Press the
key. While the keypad is running the paste
function, the display shows
for paste.
When P215 returns to 0, the parameter transfer has been
concluded. Now inveters A and B will have the same parameter
values.
P208 to P002 indicate the
speed in rpm
60
30
20
Notes
-
Transfers the current parameter values
of the inverter to non volatile memory
(EEPROM) of the HMI-CFW08-RS keypad.
The current inverter parameters are not
changed.
Transfers the content of the non volatile
memory of the keypad (EEPROM) to the
current inverter parameters.
key. During running of the
, an abbreviation
.
83