Trane IntelliPak I Programming, Troubleshooting Manual page 90

Commercial single zone rooftop air conditioner with variable air volume (vav) controls
Table of Contents

Advertisement

System Programming SETPOINTS
Supply Air Temperature Deadband
Cooling: 8.0 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable)
Default Daytime Warmup SETPOINTS
Cooling: 67 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable)
Default Occupied Zone Temp SETPOINTS
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable)
Default Unoccupied Zone Temp SETPOINTS
Cool:
85 F
Default Unoccupied Zone Temp SETPOINTS
Cool: 85 F
Heat: 60 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable)
90
Heating: 4.0 F
Terminate: 71 F
Heat: 71 F
OR
Morn Warmup: 72 F
Used With: All Units with Electric,
Hydronic, or Modulating Gas
Factory Presets: Cooling: 8 F, heat: 4 F
Possible Values:
Cooling:4 F to 20 F,
Heat: 2 F to 10 F
Used With: All units with Gas,
Hydronic, Electric, or External Heat
installed.
Factory Presets: Initiate: 67 F,
Terminate: 71 F
Possible Values:
DWU Initiate: 50 F to 87 F
DWU Terminate: 53 F to 90 F
Used With: All Units when Gas
Electric, Hydronic or External Heat is
installed and Daytime warmup is
enabled.
Factory Presets: Heat: 71 F,
Possible Values: Heat: 50 F to 90F
This is the SETPOINT to which the
heat is controlled during Daytime
Warmup mode.
Used With: All Units
Factory Presets: 85 F
Possible Values: 52 F to 90 F
Used With: All Units when Gas
Electric, Hydronic or External Heat is
installed.
Factory Presets: Cool: 85 F, Heat:
60 F, Morning Warmup: 72 F
Possible Values: Cool: 52 F to 90F,
Heat: 50 F to 88F, Morning Warmup:
50 F to 90 F.
Minimum difference of 2 degrees F
maintained between Heating &
Cooling SETPOINTS. Morning
warmup cannot be lower than
Heating SETPOINTS.
RT-SVP04F-EN