Trane IntelliPak I Programming, Troubleshooting Manual page 113

Commercial single zone rooftop air conditioner with variable air volume (vav) controls
Table of Contents

Advertisement

Relay State =
Mod Gas Heat/Chilled Water Output
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed
(if applicable).
CHILLED WATER
Actuator
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed
(if applicable).
Hydronic Heat
Actuator
0%
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice
3. Press the NEXT key until the following screen is displayed.
Modulating Gas Heat
Actuator
0%
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice
3. Press the NEXT key until the following screen is displayed.
Heat Stages: 0
K11: OFF
K12: OFF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice
3. Press the NEXT key until the following screen is displayed.
RT-SVP04F-EN
System Testing & Troubleshooting
HEAT ON
0%
0%
K1: OFF
Used With: Air Handlers with
Chilled Water Cooling and
Modulating Gas Heat installed.
Possible Values: Relay State=
HEAT ON, COOL ON; 0-100%
Used With: Air Handlers with
Chilled Water Cooling and Heat type
is not Hydronic or Mod Gas Heat.
Possible Values: 0-100%
Used With: All Rooftop Units when
Hydronic heat is installed and Air
Handlers when DX Cooling is
installed
Factory Presets: 0%
Possible Values: 0 - 100%
Used With: All Rooftop Units when
Modulating Gas is installed and Air
Handlers when DX Cooling is
installed
Factory Presets: 0%
Possible Values: 0 - 100%
Used With: All Units when Staged
Gas Heat or electric Heat is installed
Factory Presets: OFF
Possible Values: OFF, ON, Heat
Stages: 0-6