Return Fan Status Sumbenu Screens - Trane IntelliPak I Programming, Troubleshooting Manual

Commercial single zone rooftop air conditioner with variable air volume (vav) controls
Table of Contents

Advertisement

End of Submenu (NEXT) to Enter STATUS
1. Press the NEXT key to leave the submenu and show following
screen.
2. Press PREVIOUS to page back through the submenu.
RETURN FAN STATUS SUBMENU SCREENS
Note: Return Fan and Energy Recovery are mutually exclusive
features. Only one of the following two status submenus will
be displayed.
Return Fan Status Submenu
Press ENTER to View Data in This Submenu
1. Pressing the NEXT key will bypass this section.
Return Fan Relay:
Return Airflow Proving:
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that
screen to the custom menu. Refer to the custom menu for the
creation and maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed.
(if applicable)
Return Fan VFD Command:
Return Plenum Pressure:
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that
screen to the custom menu. Refer to the custom menu for the
creation and maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed.
(if applicable)
Note: Top line shown only if Return Fan VFD is installed.
RT-SVP04F-EN
Used With: All units with Return
Fan installed.
ON
Used With: All units with Return
Fan installed.
ON
Possible Values: ON, OFF
45%
Used With: All units with Return
Fan installed.
0.8 IWC
Possible Values: 0 to 100%; -0.7
to 3.5 IWC
System Operating Status
37