Trane IntelliPak I Programming, Troubleshooting Manual page 104

Commercial single zone rooftop air conditioner with variable air volume (vav) controls
Table of Contents

Advertisement

System Configuration
Configuration - Model Num Digit
Condenser Type:
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Note: For WATER-COOLED possible values the unit must be physically configured with water-cooled
condensers or improper operation and possible unit damage may occur.
Configuration - Model Num Digit
Dehumid w/ Hot Gas Reheat:
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Note: This feature uses a hardware configuration jumper and is not HI adjustable.
Configuration - Model Num Digit
Hot Gas Bypass:
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Note: If Hot Gas Bypass is installed Low Charge Protection and
Lead/Lag functions will be automatically disabled.
Configuration - Model Num Digit
Ambient Control:
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Note: When set to "STANDARD" the Low Abient Compressor
Lockout setpoint may not be set less than 40 F . When set
to "0 DEGREE F" the setpoint can be set down to -20 F .
Configuration - Model Num Digit
Remote Human Interface
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
104
27
Used With: All IntelliPak II Units
Air-Cooled
Possible Values: CONFIG REQ'D, AIR-
COOLED, WATER-COOLED W/O SUMP
HT, WATER-COOLED WITH SUMP HT
30 or 22
Used With: All IntelliPak Units
NOT INSTALLED
Possible Values:
NOT INSTALLED, INSTALLED
30 or 22
Used With: All Units
INSTALLED
Possible Values: CONFIG REQ'D, NOT
INSTALLED, INSTALLED
31 or 19
Used With: All Units
STANDARD
Possible Values: CONFIG REQ'D,
STANDARD, 0 DEGREE F
33 or 30
Used With: All Units
INSTALLED
Possible Values: CONFIG REQ'D, NOT
INSTALLED, INSTALLED
RT-SVP04F-EN