Trane IntelliPak I Programming, Troubleshooting Manual page 42

Commercial single zone rooftop air conditioner with variable air volume (vav) controls
Table of Contents

Advertisement

System Operating Status
Active Occ Humidification Setpt From
HI (Keypad) Setpoint Menu is _________
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that
screen to the custom menu. Refer to the custom menu for the
creation and maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed.
(if applicable)
Active Unocc Humidification Setpt From
HI (Keypad) Setpoint Menu is_____________
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that
screen to the custom menu. Refer to the custom menu for the
creation and maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed.
(if applicable)
Active Econ DB Enable SETPOINT From
HI (Keypad) Setpoint Menu is__________
1. Press the NEXT key until the following screen is displayed. (if applicable)
Active OA Damper Min Position STP From
HI (Keypad) Setpoint Menu is_________
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that
screen to the custom menu. Refer to the custom menu for the
creation and maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed.
(if applicable)
42
40%
20%
75 F
25%
Used With: All units with Occupied
Humidification option enabled.
Possible Values: HI (KEYPAD)
SETPOINT MENU, GBAS 0-5VDC
Module, BAS/Network, GBAS 0-10
vdc Module; Range= 20 to 50%
Used With: All units with
Unoccupied Humidification option
enabled.
Possible Values: HI (KEYPAD)
SETPOINT MENU, GBAS 0-5VDC
Module, BAS/Network, GBAS 0-10
vdc Module; Range= 20 to 50%
Used With: All Units when an
Economizer is installed
Possible Values: HI (KEYPAD)
SETPOINT MENU, GBAS 0-5VDC
Module, GBAS 0-10VDC Module;
SETPOINT range: 40 F to 90 F
Used With: All units with 0-25%
Motorized Damper or 0-100% Air
Economizer and i) OA CFM
Compensation function is DISABLED
or ii) OA Damper Min Position
SETPOINT source selection is other
than HI (KEYPAD) SETPOINT
Possible Values: HI (KEYPAD)
SETPOINT MENU, RTM Min Position
Pot, GBAS 0-5VDC Module, GBAS 0-
10VDC Module, BAS/Network;
Range from 0 to 100%
RT-SVP04F-EN