Trane IntelliPak I Programming, Troubleshooting Manual page 84

Commercial single zone rooftop air conditioner with variable air volume (vav) controls
Table of Contents

Advertisement

System Programming SETUP
Actuator Setup
Max Stroke Time
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup
Max Stroke Time
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Note: Only one of the following two screens will be shown
Actuator Setup
Min Voltage
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup
Min Voltage
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Note: Only one of the following two screens will be shown
Actuator Setup
Max Voltage
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup
Max Voltage
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Note: Only one of the following two screens will be shown
84
Num 1 Low Ambient
60 Sec
Cond Fan VFD Ckt 1
60 Sec
Num 1 Low Ambient
2.0 VDC
Cond Fan VFD Ckt 1
0.0 VDC
Num 1 Low Ambient
10.0 VDC
Cond Fan VFD Ckt 1
10.0 VDC
Used With: All Rooftop Units and
Air Handlers when DX Cooling is
installed with air-cooled condensers.
Factory Presets: 60 Seconds
Possible Values: 1 - 255 Seconds
Used With: All IntelliPak II units
with water-cooled condensers
installed.
Factory Preset: 60 seconds
Possible Values: 1-255 seconds
Used With: All Rooftop Units and
Air Handlers when DX Cooling is
installed with air-cooled condensers.
Factory Presets: 2.0 VDC
Possible Values: 0.0 to 9.9 Volts
DC
Used With: All IntelliPak II units
with water-cooled condensers
installed.
Factory Preset: 0.0 VDC
Possible Values: 0.0 - 10.0 VDC
Used With: All Rooftop Units and
Air Handlers when DX Cooling is
installed with air-cooled condensers.
Factory Presets: 10.0 VDC
Possible Values: 0.1 to 10.0 Volts
DC
Used With: All IntelliPak II units
with water-cooled condensers
installed.
Factory Preset: 10.0 VDC
Possible Values: 0.0 - 10.0 VDC
RT-SVP04F-EN