Trane IntelliPak I Programming, Troubleshooting Manual page 82

Commercial single zone rooftop air conditioner with variable air volume (vav) controls
Table of Contents

Advertisement

System Programming SETUP
Actuator Setup
Min Voltage
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed
(if applicable).
Actuator Setup
Max Voltage
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed
(if applicable).
Actuator Setup
Direct/Reverse Act
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed
(if applicable).
Actuator Setup
Max Stroke Time
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup
Min Voltage
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
82
Return Fan VFD
0.0 VDC
Return Fan VFD
10.0 VDC
Return Fan VFD
DIRECT ACTING
Exhaust Damper/VFD
60 Sec
Exhaust Damper/VFD
2.0 VDC
Used With: All units with Return
Fan installed.
0.0 VDC
Factory Presets:
Possible Values:
0.0 - 9.9 (Default
0.0)
Used With: All units with Return
Fan installed.
Factory Presets: 10.0 VDC
Possible Values: 0.0 - 10.0
(Default 10.0)
Used With: All units with Return
Fan installed.
Factory Presets: Direct Acting
Possible Values: Direct, Reverse
Used With: All Units when IGV/VFD
is installed or Return Fan is installed
Factory Presets: 60 Seconds
Possible Values: 1 - 255 Seconds
Used With: All Units when Power
Exhaust with Statitrac is installed or
Return Fan is installed.
Factory Presets: 2.0 VDC
Possible Values: 0.0 to 9.9 Volts
DC
Note: For VFD, set to 0.0 VDC; for
damper, set to 2.0 VDC
RT-SVP04F-EN