Trane IntelliPak I Programming, Troubleshooting Manual page 81

Commercial single zone rooftop air conditioner with variable air volume (vav) controls
Table of Contents

Advertisement

Actuator Setup
Direct/Reverse Act
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup
Max Stroke Time
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup
Min Voltage
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup
Max Voltage
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup
Direct/Reverse Act
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup
Max Stroke Time
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed
(if applicable).
RT-SVP04F-EN
OA Damper
DIRECT ACTING
Supply Fan IGV/VFD cmd
30 Sec
Supply Fan IGV/VFD cmd
0.0 VDC
Supply Fan IGV/VFD cmd
10.0 VDC
Supply Fan IGV/VFD cmd
DIRECT ACTING
Return Fan VFD
30 Sec
System Programming SETUP
Used With: All Units when an
economizer is installed
Factory Presets: DIRECT ACTING
Possible Values: DIRECT ACTING,
REVERSE ACTING
Used With: All Units when IGV/VFD
is installed
Possible Values: 1 - 255 Seconds
(Default 30 seconds)
Used With: All Units when IGV/VFD
is installed
Factory Presets: 0 VDC
Possible Values: 0 to 9.9 Volts DC
Note: For VFD set to 0.0 VDC
For IGV set to 2.0 VDC
Used With: All Units when IGV/VFD
is installed
Factory Presets: 10.0 VDC
Possible Values: 0.1 to 10.0 Volts
DC
Used With: All Units when IGV/VFD
is installed
Factory Presets: DIRECT ACTING
Possible Values: DIRECT ACTING,
REVERSE ACTING
Used With: All units with Return
Fan installed.
Possible Values: 1-255 seconds
(Default 30 seconds)
81