Trane IntelliPak I Programming, Troubleshooting Manual page 40

Commercial single zone rooftop air conditioner with variable air volume (vav) controls
Table of Contents

Advertisement

System Operating Status
Active Supply Air Heating STP From
HI (KEYPAD) SETPOINT MENU
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that
screen to the custom menu. Refer to the custom menu for the
creation and maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed.
(if applicable)
Active Daytime Warmup SETPOINTs
Initiate:
67 F
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that
screen to the custom menu. Refer to the custom menu for the
creation and maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed.
(if applicable)
Active Occupied Zone Heating STP From
HI (KEYPAD) SETPOINT MENU
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that
screen to the custom menu. Refer to the custom menu for the
creation and maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed.
(if applicable)
Active Unoccupied Zone Cooling STP From
HI (KEYPAD) SETPOINT MENU
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that
screen to the custom menu. Refer to the custom menu for the
creation and maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed.
(if applicable)
40
Is
100 F
Terminate:
71 F
Is
71 F
Is
85 F
Used With:
All Units when
Hydronic Heat, Electric Heat, or
Modulating Gas Heat is installed.
Possible Values: HI (Keypad)
SETPOINT Menu, Zone Sensor
SETPOINT Input, GBAS 0-5 VDC
Module, BAS/Network, GBAS 0-10
VDC Module
Used With: All Units when Gas,
Electric, Hydronic or External Heat is
installed.
Possible Values: HI (Keypad)
SETPOINT Menu; Initiate= 50-87F;
Terminate= 53-90 F (This SETPOINT
source is HI (keypad) or BAS/
Network
Used With:
All Units when Gas,
Electric, Hydronic or External Heat is
installed and Daytime Warmup
enabled.
Possible Values: HI (Keypad)
SETPOINT Menu Zone Sensor Setpnt
Input, NSB Panel SETPOINT Input,
GBAS 0-5 VDC Module, BAS/
Network, GBAS 0-10 VDC Module;
Range 50 - 88F
Used With:
All Units
Possible Values: HI (KEYPAD)
enabled.
Possible Values: HI (Keypad)
SETPOINT Menu Zone Sensor Setpnt
Input, NSB Panel SETPOINT Input,
GBAS 0-5 VDC Module, BAS/
Network, GBAS 0-10 VDC Module;
Range: 52 - 90 F
RT-SVP04F-EN