Trane IntelliPak I Programming, Troubleshooting Manual page 83

Commercial single zone rooftop air conditioner with variable air volume (vav) controls
Table of Contents

Advertisement

Actuator Setup
Max Voltage
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup
Direct/Reverse Act
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup
Max Stroke Time
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup
Min Voltage
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup
Max Voltage
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup
Direct/Reverse Act
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Note: Only one of the following two screens will be shown
RT-SVP04F-EN
Exhaust Damper/VFD
10.0 VDC
Exhaust Damper/VFD
DIRECT ACTING
Hydronic
60 Sec
Hydronic
2.0 VDC
Hydronic
10.0 VDC
Hydronic
DIRECT ACTING
System Programming SETUP
Used With: All Units when Power
Exhaust with Statitrac is installed or
Return Fan is installed.
Factory Presets: 10.0 VDC
Possible Values: 0.1 to 10.0 Volts
DC
Used With: All Units when Power
Exhaust with Statitrac is installed or
Return Fan is installed.
Factory Presets: DIRECT ACTING
Possible Values: DIRECT ACTING,
REVERSE ACTING
Used With: All Units when Hydronic
Heat and/or Chilled Water is
installed
Factory Presets: 60 Seconds
Possible Values: 1 - 255 Seconds
Used With: All Units when Hydronic
Heat and/or Chilled Water is
installed
Factory Presets: 2.0 VDC
Possible Values: 0.0 to 10.0 Volts
DC
Used With: All Units when Hydronic
Heat and/or Chilled Water is
installed
Factory Presets: 0.0 VDC
Possible Values: 0.0 to 9.9 Volts
DC
Used With: All Units when Hydronic
Heat and/or Chilled Water is
installed with air-cooled condensers
Factory Presets: DIRECT ACTING
Possible Values: DIRECT ACTING,
REVERSE ACTING
83