System Programming SETUP

Sensor Source Selections Submenu

Press ENTER to Review or Adjust
1. Pressing the NEXT key will bypass this section.
For Daytime Warmup Temp Crtl, Use sensor
Connected to: RTM ZONE TEMP INPUT
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
For Unoccupied Zone Temp Ctrl, Use Sensor
Connected To:
RTM ZONE TEMP INPUT
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
For Morning Warmup Temp Control, Use Sensor
Connected To:
RTM ZONE TEMP INPUT
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
For Space Humidity Control, Use Sensor
Connected To: RTM SPACE HUMIDITY INPUT
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed
(if applicable).
62
Used with: All Units.
Used With: All Units Gas, electric,
Hydronic or External Heat is
installed.
Possible Values: RTM ZONE TEMP
INPUT, NSB PANEL TEMP SENSOR
INPUT, RTM AUX TEMP INPUT, HEAT
MODULE AUX TEMP INPUT, ECEM
RETURN AIR TEMP INPUT
Used With: All Units
Factory Preset: RTM ZONE TEMP
INPUT
Possible Values: RTM ZONE TEMP
INPUT, NSB PANEL TEMP SENSOR
INPUT, RTM AUX TEMP INPUT, HEAT
MODULE AUX TEMP INPUT, ECEM
RETURN AIR TEMP INPUT
Used With: All Units when Gas,
Electric, Hydronic or External Heat is
installed.
Factory Preset: RTM ZONE TEMP
INPUT
Possible Values: RTM ZONE TEMP
INPUT, NSB PANEL TEMP SENSOR
INPUT, RTM AUX TEMP INPUT, HEAT
MODULE AUX TEMP INPUT, ECEM
RETURN AIR TEMP INPUT
Used With: All units with
DeHumidification or Humidification
options installed.
Factory Preset: RTM Space
Humidity Input
Possible Values: RTM Space
Humidity Input, ECEM RA Humidity
Input
RT-SVP04F-EN