Selection Of Location - Daikin RXYQ5PY1 Service Manual

R-410a heat pump 50hz/60hz cooling only 50hz
Table of Contents

Advertisement

Heat Pump / Cooling Only 50Hz (RX(Y)Q5~54P)
3.3

Selection of Location

Select a location for installation that meets the following conditions. Get the customer's
permission.
1. There is no danger of fire due to leakage of inflammable gas.
2. Select the location of the unit in such a way that neither the discharged air nor the sound
3. The foundation is strong enough to support the weight of the unit and the floor is flat to
4. The piping length between the outdoor unit and the indoor unit may not exceed the allowable
5. Locations where the unit's suction vent and outlet vent do not generally face the wind.
6. The space around the unit is adequate for servicing and the minimum space for air inlet and
Installation Space Examples
! The installation space requirement shown in figure 3 is a reference for cooling operation
! During installation, install the units using the most appropriate of the patterns shown in figure
! If the number of units installed is more than that shown in the pattern in figure 3, install the
! As regards space in front of the unit, consider the space needed for the local refrigerant
! If the work conditions in figure 3 do not apply, contact your dealer or Daikin directly.
222
generated by the unit disturb anyone.
prevent vibration and noise generation.
piping length. (Refer to "1-6 Refrigerant Piping")
Wind blowing directly into the suction or outlet vents will interfere with the unit's operation.
If necessary, install some kind of obstruction to block the wind.
air outlet is available.
(See the "Installation Space Examples" for the minimum space requirements.)
when the outdoor temperature is 35°C.
If the design outdoor temperature exceeds 35°C or the heat load exceeds maximum
capacity in all the outdoor unit, take an even large space on the intake shown in figure 3.
3 for the location in question, taking into consideration human traffic and wind.
units so there are no short circuits.
piping when installing the units.
(Pattern 1)
≥10
(Pattern 2)
≥50
(Pattern 3)
≥200
(Pattern 1)
≥10
(Pattern 2)
≥50
(Pattern 3)
≥200
< If installed as a single unit >
≥300
Service space of suction side
Front
≥10
side
≥500
Service space of front side
≥100
Service space of suction side
Front
≥50
side
≥500
Service space of front side
No limit to wall height
≥300
Front
side
< When installed in serial
≥300
Service space of suction side
≥10
≥20
Front
side
≥500
≥20
Service space of front side
≥100
Service space of suction side
Front
≥100
side
≥500
≥50
≥100
Service space of front side
No limit to wall height
≥300
≥400
≥400
Front
side
figure 3
SiEN34-705
Installation Manual