Appendix
7.15.5 [Malfunction of Transmission Examples]
Faulty Condition Caused by Branch Lines.
Applicable
VRV in general
Models
Condition
A transmission malfunction occurred when the centralized controller was added to the existing
system.
Cause
Ten of all indoor-to-outdoor lines were branch lines from a single bus cable.
Measure
Corrected IN - OUT wiring to one - after another wiring
Point of
Diagnosis
212