Appendix
7.14.2 Example 2: Mismatch between Cables Connecting Indoor and
Outdoor Units and Corresponding Piping (All Model)
Situation
The remote control is not showing any malfunction and the system is operating but there is no
flow of warm air from the indoor unit (in heating mode).
Source of
The connecting cables and the corresponding piping were not correctly matched.
Problem and
Recabling was carried out and the fault disappeared.
Remedial Action
Main Points
! Special care must be taken when the pipework and cabling are carried out by different
! Run each indoor unit in turn to check that the system is correctly matched.
196
Outdoor unit
Indoor
unit
people.
Indoor
unit
pipes
cables
Indoor
Indoor
unit
unit
General Information
SiEN34-705