SiEN34-705
2.2

Introduction

! RXYQ-P series are designed for outdoor installation and used for cooling and heatpump
! The RXYQ-P units can be combined with Daikin VRV series indoor units for air conditioning
2.2.1 Combination
The indoor units can be installed in the following range.
Note:
! Be sure to connect an R-410A indoor unit.
! At above is the total capacity and total number of units of the indoor units when configured in
Installation Manual
applications. Outdoor units come in three standard sizes, and with a single system through a
multi system combining up to three outdoor units, rated cooling capacity from 14.0 kW to 147
kW and rated heating capacity from 16.0 kW to 170 kW can be achieved.
purposes. Always use appropriate indoor units compatible with R-410A. To lean which
models of indoor units are compatible with R-410A, refer to the product catalogs.
To combine with other refrigerant indoor unit will cause malfunction.
<Outdoor unit>
<Total capacity of indoor units>
RXYQ5PYL(E) ................... 62.5 ~ 250
RXYQ8PYL(E) ................. 100
RXYQ10PYL(E) .............. 125
RXYQ12PYL(E) ............... 150
RXYQ14PYL(E) ............... 175
RXYQ16PYL(E) ............... 200
RXYQ18PYL(E) ............... 225
RXYQ20PYL(E) ............... 250
RXYQ22PYL(E) ............... 275
RXYQ24PYL(E) ............... 300
RXYQ26PYL(E) ............... 325
RXYQ28PYL(E) ............... 350
RXYQ30PYL(E) ............... 375
RXYQ32PYL(E) ............... 400
RXYQ34PYL(E) ............... 425
RXYQ36PYL(E) ............... 450
RXYQ38PYL(E) ............... 475
RXYQ40PYL(E) ............... 500
RXYQ42PYL(E) ............... 525
RXYQ44PYL(E) ............... 550
RXYQ46PYL(E) ............... 575
RXYQ48PYL(E) ............... 600
RXYQ50PYL(E) ............... 625
RXYQ52PYL(E) ............... 650
RXYQ54PYL(E) ............... 675
See the catalog for indoor unit models which can be connected.
a standard combination. See the technical reference for details on total capacity and total
number of indoor units when using a configuration other than the standard combination. The
standard combination are as follows.
<Total quantity of indoor units>
~ 400
~ 500
~ 600
~ 700
~ 800
~ 900
~ 800
~ 880
~ 960
~ 1040
~ 1120
~ 1200
~ 1280
~ 1360
~ 1440
~ 1235
~ 1300
~ 1365
~ 1430
~ 1495
~ 1560
~ 1625
~ 1690
~ 1755
Heat Pump 60Hz (RXYQ5~54P)
12 units
20 units
25 units
30 units
35 units
40 units
45 units
40 units
44 units
48 units
52 units
56 units
60 units
64 units
64 units
64 units
61 units
64 units
64 units
64 units
64 units
64 units
64 units
64 units
64 units