Daikin RXYQ5PY1 Service Manual Page 137

Daikin r-410a heat pump 50hz/60hz cooling only 50hz.
Hide thumbs

Advertisement

SiEN34-705
<The Example of A Wrong Pattern>
Wrong
×
Oil is collected to the outdoor
unit at the time of a stop,
because of bottom omission of
piping.
Wrong
×
Oil is collected to the low level outdoor
unit at the time of a stop, because of
downward slope of piping.
Good
#
Outdoor Unit - Multi Connection Piping Kit
Max.allowable
Multi Connection Piping Kit - Indoor Unit
Piping Length
REFNET Joint - Indoor Unit
Outdoor Unit - Outdoor Unit
Allowable Level
Outdoor Unit - Indoor Unit
Difference
Indoor Unit - Indoor Unit
Note: H Available on request if the outdoor unit is above.
General Information
The example of installation on which oil is not collected.
Good
#
Vertical
Projection
(V3039)
Actual piping length 10m or less, equivalent length 13m or less
Actual piping length 165m or less, equivalent length 190m or less, the
total extension 1000m or less
Actual piping length 40m or less
(Refer to Page 285, 286 Note 2 in case of up to 90m)
5m or less
50m or less
H 90m or less
(when an outdoor unit is lower than indoor units: 40m or less in case of
RX(Y)Q5P)
15m or less
Appendix
(V3040)
131